User menu:
If the legionella sequence does not reach 60 °C, +-1 °C in hysteresis within 72
hours, an alarm no. 10 in the "Alarm" menu will appear and the upper LED
will flash in red light and the heat pump will turn back to normal operating
mode.
Note! The alarm will reset automatically after a new successfully legionella
sequence.
User menu:
In the "status" menu the user can see the information "H.Water" which tells
that the heat pump is running in normal operating mode when the legionella
alarm is activated.
User menu:
The user can push the button on the "Alarm" menu to acknowledge the
alarm.
Note! If the error appears again please contact an installer.
Other information:
If a legionella sequence is active and the user turns off the function, the
ongoing sequence will be deactivated.
If a power cut has occurred, the sequence will be restarted and start from
when the power has returned and by this the user should manually turn off
the function and start it again from the desired time.