see "page 12 wiring diagram for connection to controller.
SC-HP
5°C – T max
52°C
Set point temperature of "HP only "operating mode, when Solcel function activated (inverter signal)
SC-EL
5°C – T max
53°C
Set point temperature of "EL only " or "HP + EL" operating mode, when Solcel function activated (inverter
signal)
Holiday
This parameter activates/deactivates the holiday mode. The holiday mode can be selected with the
rotary/push button. The possible selection are:
Off
"Off", "1 week", " 2 weeks", "3 weeks", "3 days", "Manual"
When the holiday mode is activated, "T2 min" is the safety level for frost protection..
Man.days
This parameter displays the number of holidays at individual (manual) choice. The holiday days can be
selected with the rotary/push button. The possible selection are:
1
1-99
ReDays
This parameter displays status of the remaining number of holidays. The possible values are
0
0-99
Boost
This parameter activates/deactivates the BOOST operating mode in the case of additional need for DHW.
If the BOOST operating mode is activated "ON", the DHW production will be made by the HP and the
Off
supplementary electrical heating either for a maximum cycle of 1 hour or if Tmax is reached. Possible
values
"Off", "On". The factory setting is "OFF".
FanPause
"Off", "30m/15s", "30m/30s" , "60m/15s", "60m/30s" , "90m/15s", "90m/30s"
30
When activated the fan will stop for either 15 or 30 seconds every 30m, 60m or 90m, according to the
selected value.

SERVICE MENU

ONLY FOR THE INSTALLER

Language
Danish, German, English, Spanish, French, Polish, Slovene, Italian
English
Software
SERVICE MENU – Only for the installer.
1.58
The menu "software" indicates the software release.
The number "1.58" is the actual release
Defrost
SERVICE MENU – Only for the installer.
Gas
This parameter displays the selected defrosting mode. Attention: The defrosting mode is model
specific and must not be changed without written consent of the manufacturer.
The possible selections are:
"GAS", for BWP 270 0A / BWP 270 1A
Service Def.None, Def.Gas
Anode
SERVICE MENU – Only for the installer.
Off
"Off", "On"
Is activated if signal anode is factory installed or can be activated if signal anode is retrofit.
T max
SERVICE MENU – Only for the installer
55°C
Maximum operating "T max". This parameter value limits the maximum operating temperature.
Here can the maximum desired operating temperature be adjusted. ".
"T max" can be adjusted in between 5°C and 62°C. The DHW set point temperature cannot exceed
Tmax. Please note, that efficiency of the heat pump is reduced at higher temperatures = higher
energy consumption.
Legionel
This parameter displays status of the automatic Legionella protection mode.
Off
If activated ("ON") the DHW HP will once a week increase the DHW temperature to 60°C using the
heat pump and electrical heating, in order to avoid possible bacteria (legionella) creation. (see page
28 for using the legionella function)
Compressor protection: After each compressor stop, a new start is delayed at least 5 minutes.

FAN CONTROL:

The fan has 2 speed settings, which can be adjusted in the menu "FanOper". The factory setting for the parameter value
is "high". We recommend this setting for best performance. Nevertheless, if necessary, the "low" speed setting can be
15