Mounting Heating-/Cooling Energy Meter; Installation Of The Temperature Sensors - Zenner ENERGIETECHNIK zelsius C5 - IUF Manuel De Montage Et D'installation

Masquer les pouces Voir aussi pour ENERGIETECHNIK zelsius C5 - IUF:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Deutsch
English
Mounting heating-/cooling ener-
gy meter
Flush the system thoroughly be-
fore installing the heating-/cooling
energy meter.
Close valves and release pres-
sure.
Dismount the existing flow sensor
or meter blank.
Use only new and flawless sealing
material and check the seal face
for damage.
Install the new flow sensor accor-
ding to the correct flow direction
and installation position.
Turn heat computer to desired
reading position.
Installation of the temperature
sensors
The installation of the tempera-
ture sensors should be preferably
symmetrical and direct installati-
on.
Do not remove the return sensor
if already mounted on the VMU.
This is also valid for all the safety
seals which are mounted on the
device as a standard.
Sensors
(according
red= Supply (the hot side in
Supply
Return
Symmetrical sensor installation for zelsius
C5-IUF with the return sensor integrated in the
measuring capsule.
24
Français
are
colour-coded
to
the
model):
Consumer
„Heating" mode and the cold
side
in
blue= Return (the cold side in
„Heating" mode and the hot side
in „Cooling" mode).
The connecting cables may not
be buckled, extended or shor-
tened.
The seal at the sensor installation
point on the measuring capsule
may not be damaged.
Remove locking screw and seal
at the ball valve completely, if
existing.
Attach the O-ring to the installa-
tion aid (the 2nd O-ring is only a
spare O-ring). Using the installa-
tion aid, insert the O-ring into the
installation point according to DIN
EN 1434 with a slight circular mo-
tion.
Using the other end of the instal-
lation aid bring the O-ring into the
correct position.
Insert the 2 halves of the plastic
connector into the sensor's three
notches (crimps) and press them
together.
Use the installation aid as positi-
oning aid.
Insert the temperature sensor
into the installation point and
Supply
Return
Symmetrical sensor installation for zelsius
®
C5-IUF.
in
„Cooling"
mode);
Consumer
®

Publicité

Table des Matières
loading

Table des Matières