Installation flow sensor (FS)

Mount ball valves up- and down-
stream of the flow sensor.
Consider the correct installation
point. Normally this is the return
(the colder pipe in heating sys-
tems). Please note the type plate
information.
Consider the correct flow direc-
tion. This is indicated by an arrow
on the side of the flow sensor.
Do not install at highest point of
piping to avoid air inside the flow
sensor.
Consider the dimensions of the
heat meter.

Installation of the ball valve

Mount ball valves up- and down-
stream of the meter.
Mount a ball valve with bore
M10x1 for the temperature sensor
installation.
For symmetrical temperature sen-
sor installation, mount a second
identical ball valve.

Mounting heat/cooling energy meter

Flush the system thoroughly
before installing the heat/cooling
energy meter.
Close valves and release pressure.
Dismount the existing flow sensor
/ fitting.
Use only new and flawless sealing
material, no hemp or similar!
Clean sealing surfaces and check
for damage.
Install the new flow sensor ac-
cording to the correct flow direc-
tion and installation position.
Turn heat computer to desired
reading position.
Supply
Return
Asymmetrical sensor installation for
zelsius® C5-ISF with one temperature sensor
integrated in the flow sensor
Installation of the temperature
sensors
Supply
Consumer
Return
Symmetrical sensor installation for
zelsius® C5-ISF
The installation of the tempera-
ture sensors should be prefer-
ably symmetrical and as direct
installation.
Do not remove the temperatur
sensor if already mounted on
the flow sensor. This is also valid
for all the safety seals which are
mounted on the device as a
standard.
Sensors are colour-coded
(according to the model):
Red = Pipe with higher tempera-
ture level (supply in „Heating"
mode and return in „Cooling"
mode)
Blue = Pipe with lower tempera-
ture level (return in „Heating"
mode and supply in „Cooling"
mode)
The connecting cables may not be
buckled, extended or shortened!
The seal at the sensor installation
point on the flow sensor may not
be damaged.
Remove locking screw and seal
at the ball valve completely, if
existing.
Attach the O-ring to the installa-
tion aid (the 2nd O-ring is only a
spare O-ring). Using the installa-
tion aid, insert the O-ring into the
installation point according to
DIN EN 1434 with a slight circular
motion.
Using the other end of the instal-
lation aid bring the O-ring into the
correct position.
Consumer
17