Step. 7 Reinsert the blower assembly with the motor now on the left into the air handler cabinet and reuse the (2)
screws that secured the fan assembly in position. Reroute the connector for the motor back into the enclosure and
reconnect. Reinstall Control Box.
NOTE
The wiring harness might have to be removed from the plastic retainers mounted to the motor bracket
in order to have sufficient length to reach the electrical enclosure mounted to the fan assembly.
Ensure wiring harness is secure so it cannot be pulled into the fan.
Step. 8
A. Disconnect the waterproof thermistor harness inside the coil portion of the cabinet.
B. Remove the brackets which secure the coil assembly.
C. Slide the coil assembly out of the air handler cabinet.