Fan assembly rotation not required
9.3. Horizontal left installations
For horizontal left installation the drain pan will need to be moved to the opposite side of the coil. This can be done by
moving the two brackets and drain pan to the left of the coil. This way, the condensate that formed on the coil will fall in the
drain pan. Also, the appropriate knockouts for the drains will need to be removed once the drain pan is in its correct
position. In addition to relocating the side drain pan, the fan assembly will also need to be removed rotated 180° and
reinstalled. The motor has to be closest to the ground. The two clear plastic tubes included in the accessory bag will also
need to be attached to the top drain pan. See instructions below.
Directions for rotating fan for Horizontal Left Installation:
Step. 1 Remove the panel marked "FILTER".
Specifications are subject to change without notice.
NTXAMT12, 18, 24, 30, 36A112AA
⑤ Electrical Knockouts
⑧ Auxiliary Drain Pan
⑨ Primary Drain 3/4" FPT
⑩ Airflow
Horizontal Right
20
© 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.