3.3. Before getting started
CAUTION
• Do not install the unit where combustible gas may leak.
– If the gas leaks and accumulates around the unit, an explosion may result.
• Do not use the air conditioner in special environments.
– Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of the air conditioner or
damage its parts.
• When installing the unit in a hospital, communication station, or similar place, provide sufficient
protection against noise.
– The INVERTER equipment, private power generator, high-frequency medical equipment, or radio
communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On
the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical
treatment of image broadcasting.
• Do not install the unit on a structure that may cause leakage.
– When the room humidity exceeds 80% or when the drain pipe is clogged, condensation may drip from
the indoor unit. Perform collective drainage work together with the outdoor unit, as required.
• When the ambient dew point temperature exceeds 75°F (24°C), dew condensation may occur on the
unit surface. Perform appropriate treatment to avoid dew condensation.