10.4. Horizontal right installation
The PAA unit is shipped from the factory for horizontal right configuration, no further changes are required.
If the heat exchanger assembly is removed, please follow steps 1-10 (Vertical orientations- see "Upflow/
Downflow installation" section) in reverse order to replace the heat exchanger back in the cabinet.
CAUTION
Auxiliary drain pan requirement
An auxiliary drain pan without a separate drain line shall be installed under the cabinet of
the PAA unit. The pan must have a minimum depth of 1.5 inches (38 mm), be not less than
3 inches (76 mm) larger than the unit or the coil dimensions in width and length and must
be constructed of corrosion-resistant material. Galvanized sheet steel pans must have a
minimum thickness of not less than 0.0236-inch (0.6010 mm). (Do not use 24 gauge.)
Non-metallic pans must have a minimum thickness of not less than 0.0625 inch (1.6 mm).
This pan must be equipped with a water level detection device conforming to UL 508 that
will shut off the equipment served prior to overflow of the pan. The pan must be equipped
with a fitting to allow for drainage.
Specifications are subject to change without notice.
PAA-A18, 24, 30, 36, 42AA1/BA1/CA1
57
© 2022 Mitsubishi Electric US, Inc.