LA 0712C
5
Transport
CAUTION!
When transporting the heat pump, ensure that it is not tilted
by more than 45° (in any direction).
A pallet should be used to transport the heat pump to its final
installation location. The basic device can be transported with a
lift truck, hand truck or by means of 3/4" pipes fed through the
holes in the baseplate or frame.
The heat pump and the transport pallet are joined by four tran-
sit bolts. These must be removed.
Before using the transport holes in the frame, it is necessary to
remove the two side panel assemblies. Each covering panel is
secured with two screws. After the screws are loosened, the
panels must be tilted and pulled out of the kickplate.
The top fan panel, which does not have to be removed for
transportation, can be hung out of the cover panel. Rehang the
panel by gently pushing it in an upwards direction.
NOTE
Be careful not to damage any components when inserting the
pipes through the frame.
All black dust caps must be snapped back into the transport
holes at the installation location.
After transportation, the transport fastening in the device is to
be removed from both sides of the base.
www.glendimplex.de
CAUTION!
Before commissioning, the transport fastening must be
removed.
452168.66.30 · FD 0210
English
Remove/screw in
transport lock