Installation
6.1 General
The device must be installed on a permanently level, smooth
and horizontal surface. The frame around the device must lie
tightly against the floor to guarantee adequate sound insula-
tion, to prevent water-bearing parts from cooling out and to
protect the inside of the device from small animals. If this is not
the case, additional insulation measures may be necessary. To
prevent small animals from entering the inside of the device, it
may be necessary to seal the connection hole in the base plate,
for example. Furthermore, the heat pump should be set up so
that the air outlet direction of the fan is perpendicular to the
main wind direction to allow unrestricted defrosting of the
evaporator. The heat pump is designed for installation on even
ground. In the case of different conditions (e.g.: installation on a
platform or flat roof) or there is a greater risk of the heat pump
tipping over (due to an exposed position or high wind expo-
sure), additional protection against tipping over must be pro-
vided. The responsibility for the heat pump installation lies with
the specialist system construction company. During the instal-
lation, local requirements such as building regulations, static
load of the building, and wind exposure must be accounted for.
It must be possible to carry out maintenance work without hin-
drance. This is ensured when observing the distances to solid
walls as shown in the figure.
0,4 m
0,5 m
≥ 0 m
The specified dimensions are valid for stand-alone installation
only.
CAUTION!
Do not restrict or block the area around the air intake or outlet
area.
CAUTION!
Observe country-specific building regulations!
CAUTION!
The physical impacts must be observed for installation close
to walls. No windows or doors should be present in the area
surrounding the air outlet of the fan.
CAUTION!
In cases of installation close to a wall, there may be more
sediment in the air inlet and outlet areas due to the air current.
The colder outside air outlet should discharge in such a way as
to not increase the heat losses in heated neighbouring rooms.
EN-6
CAUTION!
Installation in a hollow or in an inner courtyard is not
permitted because cooled air collects at ground level and is
drawn in again by the heat pump during extended periods of
operation.
6.2 Condensate pipe
Condensed water that forms during operation must be drained
off frost free. To ensure proper drainage, the heat pump must
be mounted horizontally. The condensate pipe must have a
minimum diameter of 50 mm and must be fed into a sewer in
such a way that it is safe from frost. Do not discharge the con-
densate directly into clearing tanks or cess pits. The aggressive
vapours and a condensate pipe laid in an area which is not
frost-free can destroy the evaporator.
CAUTION!
The frost line can vary according to the climatic region. The
regulations of the countries in question must be observed.
2,0 m
7
Assembly
7.1 General
The following connections need to be established on the heat
pump:
Flow and return of the heating system
Condensate drain
Control cable to the heat pump manager
Power supply
To access the inside of the device, all side panel assemblies can
be removed as described in Cap. 5 on pag. 5.
452168.66.30 · FD 0210
LA 0712C
www.glendimplex.de