Installation and set-up / operation
Check the safe functioning of the unit. The operation is maintenance-
free. Failure indication:
Above measuring range by more than 3% of the maximum
value.
Below measuring range by more than 10% of the minimum
value.
Flashing: Short-circuit in the switching output (OUT 1).
The output is switched off as long as the short circuit continues.
Flashing: No temperature sensor connected,
fault or short circuit in the temperature sensor,
wire break, evaluable range (T < -60°C or T > +320°C)
exceeded.
In case of a fault or short circuit in the sensor the outputs switch ON or OFF
depending on the setting of the parameter FOUx;
Response of the analogue output:
• Falling below the set measuring range leads to a linear decrease
of the analogue signal up to 3.8 mA / 0 V.
• Exceeding the set measuring range leads to a linear increase to
20.5 mA / 10.3 V.
• If the current system temperatur is below or above the evaluable
range of the sensor (T < -60°C or T > +320°C), the output
responds according to the parameter set in FOU2 (→ page 26).