Response of the switching output in case of a fault
(fault or short circuit in the sensor).
2 settings can be selected:
• FOU1 = ON: output switches ON in case of a fault
• FOU1 = OFF: output switches OFF in case of a fault
Response of the analogue output in case of a fault
(fault or short circuit in the sensor).
2 settings can be selected:
• FOU2 = ON: The analogue signal goes to the value 21.0 mA /
10.6 V.
• FOU2 = OFF: The analogue signal goes to the value 3.5 mA /
0 V.
Output polarity of the switching output
2 options can be selected:
• PnP = positive switching
• nPn = negative switching
Setting of the display
7 options can be selected:
• d1 = update of the measured value every 50 ms
• d2 = update of the measured value every 200 ms
• d3 = update of the measured value every 600 ms
The update interval only refers to the display. It has no effect on
the outputs.
• rd1, rd2, rd3 = display as d1, d2, d3; rotated 180°
• OFF = In the Run mode the display of the measured value is
deactivated. If one of the buttons is pressed, the current mea-
sured value is displayed for 15 s. Another press of the
Mode/Enter button opens, the Display mode. The switching
status LEDs remain active even if the display is deactivated.
Display unit
The measured value and the values for SP1, rP1, ASP, AEP and
COF can be displayed in the following units:
°C , °F
Select the display unit before setting the values for SP1, rP1,
ASP, AEP and COF. This avoids rounding errors generated inter-
nally during the conversion of the units and enables exact set-
ting of the values.
Units are delivered from the factory with: Uni = °C
26