Setting the measurement method
2 settings can be selected:
• 3w : 3-wire measurement
• 4w : 2-wire and 4-wire measurement
Enhanced functions
This menu item contains a submenu with additional parameters.
You can access these parameters by pressing the SET button
briefly.
Min-Max memory for system temperature
• HI: displays the highest measured temperature
• LO: displays the lowest measured temperature
In case of a wire break or value above or below the measuring
range "Err" is stored.
Erase the memory:
- Press the "Mode/Enter" button until HI or LO is displayed.
- Press the "Set" button and keep it pressed until "- - - -"
is displayed.
- Then press the "Mode/Enter" button briefly.
It is recommended to erase the memory as soon as the unit
starts working under normal operating conditions.
Calibration offset
The internal measured value (operating value of the sensor) is
offset against the real measured value.
°C
°F
Calibration reset
Resets the calibration set by COF
- Press the "Mode/Enter" button until CAr is displayed.
- Press the "Set" button and keep it pressed until "- - - -" is
displayed.
- Then press the "Mode/Enter" button briefly.
Delay time for the switching output
dS1 = switch-on delay; dr1 = switch-off delay
The output does not immediately change its switching status
when the switching condition is met but when the delay time
has elapsed. If the switching condition is no longer met when
the delay time has elapsed, the switching state of the output
does not change.
• Setting range: 0 / 0.10 ... 50 s in steps of 0.1 s
(0 = delay time is not active),
• indicated in seconds.
setting range
-10.0 ... +10.0
-18.0 ... +18.0
in steps of
0.1
0.1
25