ture.
The LED display indicates the current system temperature.
The yellow LED indicates the switching state of the transistor output.
The green LESs indicate the set display unit (°C or °F).
Display mode:
Indication of parameters and the set parameter values
When the "Mode/Enter" button is pressed briefly, the unit passes to
the Display mode which allows parameter values to be read. The inter-
nal sensing, processing and output functions of the unit continue as if
in Run mode.
• The parameter names are scrolled with each pressing of the
"Mode/Enter" button.
• When the "Set" button is pressed briefly, the corresponding para-
meter value is displayed for 15 s. After another 15 s the unit returns
to the Run mode.
Programming mode:
Setting of the parameter values
While viewing a parameter value pressing the "Set" button for more
than 5 s causes the unit to enter the programming mode.You can alter
the parameter value by pressing the "Set" button and confirm the
new value by pressing the "Mode/Enter" button. The internal sensing,
processing and output functions of the unit continue as if in Run
mode with the original parameter values unless a new value is con-
firmed.
The unit returns to the Run mode when no button has been pressed
for 15 s.
Installation
Connect a temperature sensor to the unit and fix it to the process
connection.