Electrical connection
The unit must be connected by a suitably qualified electrician.
The national and international regulations for the installation of
electrical equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
Referring to UL: For use on a low voltage circuit with overcurrent
protection in accordance with UL873 Tab. 28.1 or Imax =
100/Ub (Ub = voltage of the circuit).
Disconnect power before connecting the unit as follows:
2
3
4
Two-wire
1
sensor
Three-wire
2
sensor
Four-wire
3
sensor
Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4 = BK (black)
All manuals and user guides at all-guides.com
1
BN
2
WH
1
4
BK
4
3
BU
pnp
1
1
2
3
1
2
3
4
ϑ
Menu setting: Mmod = 4w,
links between 1 / 2 and 3 / 4.
A wiring fault can be corrected in the menu COF.
Menu setting: Mmod = 3w, link between 1 / 2.
The maximum cable resistance of 10 Ω per core must
not be exceeded (this corresponds to a cable length of
approx. 80 m for a wire cross-section of 0.14 mm²).
Menu setting: Mmod = 4w.
L +
npn
L
2
1
2
3
4
ϑ
1
BN
L +
2
WH
4
BK
3
BU
L
2: OUT2
4: OUT1
3
2
3
4
1
ϑ
21