Outside Lockout Temperature
Adjustment
To adjust the outside lockout temperature limit, press
the SERVICE key and select "Outside Lockout" on the
digital display. Use the UP and DOWN keys to set the
ambient temperature at which the unit will be locked out
of operation. This setting can be adjusted in the range of
30°F to 50°F (-1°C to 10°C), with a default value of 45°F
(7°C).
Outside Lockout
Figure 34. Outside Lockout Temperature Adjustment
Brownout Detection Mode
To adjust the brownout detection mode, press the
SERVICE key and navigate to "Brownout Detect" on the
digital display. You can then use the UP and DOWN keys
to choose from three options: 230V, 208V, or Disabled.
Enabling brownout detection will cause the unit to shut
down automatically if the Transformer's 24VAC signal
drops below a certain threshold, specifically below
21VAC for 230V or below 24VAC for 208V. This function is
intended to protect the unit from low voltage situations. If
you prefer not to use this feature, simply select "Disabled".
The default setting for brownout detection is 230V.
Brownout Detect.
Figure 35. Brownout Detection Mode Option
NOTE: Disabling "Brownout Detection" limits the ability
of the heater to protect the compressor.
Installer Menu
To access the Installer Menu, press the SERVICE key
and select "INSTALLER Menu" on the digital display. You
can use the UP key to enter the Installer menu, or press
SERVICE to move to the next option. For more details on
the "Installer Menu", please refer to page 21.
APPROVED
45F
230V
UNCONTROLLED DOCUMENT IF PRINTED
INSTALLER Menu
UP key to Enter
Figure 36. Installer Menu Option
Schedule Menu
To access the SCHEDULE Menu, press the SERVICE
key and select "SCHEDULE Menu" on the digital display.
You can use the UP key to enter the Schedule menu and
editor, or press SERVICE to return to the beginning of the
Program menu. For more information on the "Schedule
Menu", please refer to page 25.
SCHEDULE Menu
UP key to Enter
Figure 37. Schedule Menu Option