12. PROGRAM MENU (
To access the PROGRAM menu, press and hold SERVICE
and MODE keys simultaneously for 7 to 10 seconds until
"Language" screen appears on the display.
This menu allows to change and reset the factory default
settings, as well as providing access to the Installers and
Schedule menus. There are different features and settings
required for different model types. This section outlines
the items noted on the display in Heat Only and Heat/Cool
configurations, the default values and range of adjustable
values and a description of the feature.
Any changes to values are stored into the non-volatile
memory after selection is made using the UP or DOWN
keys. Pressing SERVICE key toggles to the next setting.
Failure to press any key for 5-minutes will cause the screen
to return to Operation mode screen. The Program mode
can also be exited by pressing the MODE key.
CAUTION: Changes to default program configurations
could affect normal functionality of the heater.
Language Selection
The initial display in PROGRAM Menus is "Language"
selection.
The UP and DOWN keys will select English, Spanish or
French language for all menus and Display messages.
Language
English
Figure 23. Language Selection Mode
Set Factory Defaults
Press the SERVICE key again. "Set Defaults" option
is displayed. To set factory defaults, press and hold
SERVICE and MODE keys simultaneously for 3 to 5
seconds until "Defaults Set" appears. This operation
resets the operating program to its factory default values.
The pool setpoint is configured to 80°F (27°C), and the
SPA setpoints will default to 100°F (38°C). The maximum
temperature setting for pool and spa is limited to 95°F
(35°C) and 104°F (40°C), respectively. The language
is set to English, and the temperature display is set to
Fahrenheit. The cooling deadband is set to 6°F (3.5°C),
defrost temperature to 24°F (-4°C), defrost deadband
to 10°F (5.5°C) and outside lockout to 45°F (7°C),
respectively. The brownout is set to 230V, and the remote
pool mode is set to Heat. The local schedule is disabled
but not erased, and the "VS Pump Control" and other
add-ons are also disabled. Note that cooling deadband
and remote pool mode settings are only available in Heat/
Cool models.
The "Control Lockout PIN" will be cleared, and the control
will resume normal operation. See the "Control Lockout"
section on page 14.
APPROVED
+
Lenguaje
Langue
Español
Français
UNCONTROLLED DOCUMENT IF PRINTED
)
Set
Brownout Detect.
Figure 24. Set Defaults Option
Reset Faults
Press the SERVICE key again. "Reset Faults" appears
on the digital display. To clear faults history, press and
hold SERVICE and MODE keys simultaneously for 3 to 5
seconds until "Faults Cleared" appears.
This function clears the historical fault available in
SERVICE menu.
NOTE: When the unit is connected to Wi-Fi, the historical
faults can be accessed in the timeline tab of Raymote.
Reset faults do not affect historical faults registered in
Raymote.
Brownout Detect.
Reset Faults
Figure 25. Reset Faults Option
Wi-Fi Reset
Press the SERVICE key again. "Wi-Fi Reset" appears
on the digital display. To clear stored Wi-Fi signal name
and password, press and hold SERVICE and MODE keys
simultaneously for 3 to 5 seconds until "Wi-Fi Initialized"
appears.
This operation resets the Wi-Fi credentials, leaving the unit
ready to configure connection with the Raymote app. For
details on how to connect your pool heater to Raymote,
follow the instructions on page 43.
WiFi Reset
Brownout Detect.
Figure 26. Wi-Fi Reset Option
Temperature Display
Press the SERVICE key again "Temp Display" appears
on the digital display. The UP or DOWN keys will select
"Fahrenheit" or "Celsius" on the temperature display.
Choose the desired temperature scale. After making
the selection, all temperature screens will be updated to
display degrees in either Fahrenheit or Celsius.
Temp Display
Fahrenheit
Figure 27. Temperature Display Option
Defaults
Temp Display
Celsius
17