Spa Setpoint Maximum Adjustment
Press the SERVICE key again. "Spa Max Temp" appears
on the digital display. Using the UP and DOWN keys will
change the maximum temperature setting to your desired
value. The control can be set to limit the maximum setpoint
in the range of 65°F to 104°F (18°C to 40°C). The default
value is 104°F (40°C).
Spa Max Temp
Figure 28. Spa Setpoint Maximum Adjustment Option
Pool Setpoint Maximum Adjustment
Press the SERVICE key again. "Pool Max Temp" appears
on the digital display. Using the UP and DOWN keys will
change the maximum temperature setting to your desired
value. The control can be set to limit the maximum setpoint
in the range of 65°F to 95°F (18°C to 35°C). The default
value is 95°F (35°C).
Pool Max Temp
Figure 29. Pool Setpoint Maximum Adjustment Option
Cooling Deadband Adjustment -
(Heat/Cool Models Only)
Press the SERVICE key again. "Cooling Deadband"
appears on the digital display. Using the UP and DOWN
keys will change the cooling deadband setting. In POOL
AUTO mode, the cooling setpoint is the heating setpoint
minus this cooling deadband value. This setting can be set
in the range of 2°F to 10°F degrees (1°C to 5.5°C). The
default value is 6°F (3.5°C).
Cooling Deadband
Figure 30. Cooling Deadband Adjustment Option
Remote Pool Mode -
(Heat / Cool Models Only)
Press the SERVICE key again. "Remote Pool Mode"
appears on the digital display.
When Remote mode (3-wire selector) is enabled, and
the unit is a Heat/Cool model, this setting can be used to
define the operation mode of the "Pool" wire selector. Use
UP and DOWN keys to set Remote pool mode to Pool
Heat, Pool Cool or Pool Auto. The default value for remote
pool mode is "Heat".
18
APPROVED
104F
95 F
6 F
UNCONTROLLED DOCUMENT IF PRINTED
Remote Pool Mode
Figure 31. Remote Pool Mode Option
Defrost Temperature Adjustment
To adjust the defrost temperature, press the SERVICE
key and select "Defrost Temp" on the digital display. Use
the UP and DOWN keys to adjust the temperature setting,
which is measured on the coil during defrost mode. The
range of available settings is 20°F to 35°F (-6.5°C to
1.5°C), with a default value of 24°F (-4°C).
Defrost Temp
Figure 32. Defrost Temperature Adjustment Option
Defrost Deadband Adjustment
To adjust the defrost deadband, press the SERVICE key
and select "Defrost Deadband" on the digital display. Use
the UP and DOWN keys to adjust the deadband setting,
which determines when defrost mode ends based on
the coil temperature. The defrost cycle ends when the
coil temperature is higher than the Defrost Temperature
plus the Defrost Deadband. You can set this value in the
range of 5°F to 20°F (2.5°C to 11°C), with a default value
of 10°F (5.5°C).
Defrost Deadband
Figure 33. Defrost Deadband Adjustment Option
Heat
24F
10F