Fuji Electric FRENIC-HVAC Serie Manuel D'instructions page 19

Publicité

Conformité aux normes UL et celles listées par le cUL pour le Canada (suite)
Inverter type
Type de variateur
0,75
FRN0.75AR1-4
1,5
FRN1.5AR1-4
2,2
FRN2.2AR1-4
3,7
FRN3.7AR1-4
*
(4,0)
FRN4.0AR1-4E
5,5
FRN5.5AR1-4
7,5
FRN7.5AR1-4
11
FRN11AR1-4
15
FRN15AR1-4
18,5
FRN18.5AR1-4
22
FRN22AR1-4
30
FRN30AR1-4
37
FRN37AR1-4
45
FRN45AR1-4
55
FRN55AR1-4
75
FRN75AR1-4
90
FRN90AR1-4
110
FRN110AR1S-4
132
FRN132AR1S-4
160
FRN160AR1S-4
200
FRN200AR1S-4
220
FRN220AR1S-4
280
FRN280AR1S-4
315
FRN315AR1S-4
355
FRN355AR1S-4
400
FRN400AR1S-4
500
FRN500AR1S-4
630
FRN630AR1S-4
710
FRN710AR1S-4
* 4.0 kW for the EU. The inverter type is FRN4.0AR1
Note: A box (
) replaces an alphabetic letter depending on the enclosure.
A box () replaces an alphabetic letter depending on the shipping destination.
Enclosure: M (IP21) or L (IP55)
*1 Not more than 6 rms Amperes fuses or not more than 5 rms Amperes breakers for aux. control power supply and aux.
main power supply.
*2 Protect the inverter by both a circuit breaker and the fuse tabulated below connected in series.
Inverter type
FRN45AR1-4
FRN55AR1-4
FRN75AR1-4
FRN90AR1-4
3
5
6
10
10
15
20
15
25
20
35
30
50
40
60
50
70
100
75
125
100
100 (*2)
150 (*2)
-
175 (*2)
200 (*2)
350
250
400
300
500
350
600
500
-
600
-
800
-
-
1200
-
-
1400
-
1600
-4E.
Shipping destination: E (Europe) or A (Asia) or other code except "U"
Fuse type
Made by Mersen
A70QS250-4
A70QS350-4
xvii
Required torque
Couple requis
lb-in
Main
Control
terminal
circuit
Borne
Circuit de
principale
commande
15,9
(1,8)
51,3
(5,8)
119,4
(13,5)
6,1
(0,7)
238,9
(27)
424,7
(48)
Made by Bussmann
FWP-250A
FWP-350A
(N•m)
Aux. control
Aux. main
power
power supply
supply
Aux. princi-
Alimentation
pale
électrique de
source d'ali-
commande
mentation
aux.
-
10,6
(1,2)
10,6
(1,2)