Conformité aux normes UL et celles listées par le cUL pour le Canada (suite)
12. Install UL certified fuses or circuit breaker between the power supply and the inverter, referring to the table
below. The tightening torque is as follows.
Installez les fusibles certifiés UL ou un disjoncteur entre l'alimentation électrique et le variateur, en vous
référant au tableau ci-dessous. Le couple de serrage est comme suit.
■kW rating (Valeur kW)
Inverter type
Type de variateur
0,75
FRN0.75AR1-2
1,5
FRN1.5AR1-2
2,2
FRN2.2AR1-2
3,7
FRN3.7AR1-2
*
(4,0)
FRN4.0AR1-2E
5,5
FRN5.5AR1-2
7,5
FRN7.5AR1-2
11
FRN11AR1-2
15
FRN15AR1-2
18,5
FRN18.5AR1-2
22
FRN22AR1-2
30
FRN30AR1-2
37
FRN37AR1-2
45
FRN45AR1-2
55
FRN55AR1S-2
75
FRN75AR1S-2
90
FRN90AR1S-2
* 4.0 kW for the EU. The inverter type is FRN4.0AR1
Note: A box (
) replaces an alphabetic letter depending on the enclosure.
A box () replaces an alphabetic letter depending on the shipping destination.
Enclosure: M (IP21) or L (IP55)
*1 Not more than 6 rms Amperes fuses or not more than 5 rms Amperes breakers for aux. control power supply and aux.
main power supply.
*2 Protect the inverter by both a circuit breaker and the fuse tabulated below connected in series.
Inverter type
FRN22AR1-2
FRN30AR1-2
FRN37AR1-2
FRN45AR1-2
5
10
10
15
15
25
20
35
30
50
40
70
50
100
75
125
100
100 (*2)
150 (*2)
-
175 (*2)
200 (*2)
350
250
500
350
600
400
-2E.
Shipping destination: E (Europe) or A (Asia) or other code except "U"
Fuse type
Made by Mersen
A70QS250-4
A70QS350-4
xv
Required torque
Couple requis
lb-in
Control
Aux. control
Main
circuit
power supply
terminal
Circuit
Alimentation
Borne
de
électrique de
principale
com-
commande
mande
15,9
(1,8)
51,3
(5,8)
6,1
(0,7)
119,4
(13,5)
238,9
(27)
424,7
(48)
Made by Bussmann
FWP-250A
FWP-350A
(N•m)
Aux. main
power supply
Aux. principale
source d'alimen-
tation
aux.
-
10,6
(1,2)
10,6
(1,2)

Publicité