b.
Press and hold the Display toggle for 4 seconds.
If the machine is in the Battery Mode, it enters the silent mode. Press again for 4 seconds
and it will return to normal (buzzer) mode.
If the machine is in the Line Mode, it proceeds to Self Test.
c.
If the Display toggle remains untouched for over 30 seconds, the LCD backlight will turn off
automatically.
SET-UP MODE
Step 1: Hold the Display toggle for 10 seconds to enter the EPS set-up Mode. LCD icon 1, 2 lights
indicate Set-Up Mode.
Step 2: By pressing the Display toggle, users can switch between setup functions. User configurable
functions are as follows:
a.
Delay Time: The time delay between switching from Battery Mode to Line Mode. There are 9
different settings. The default setting is 0 minute.
Function description: The machine will switch from Battery Mode to Line Mode after the AC
power transmission reaches stability within the preset delay time.
b.
Charging Current: The function adjusts the battery charging current according to the capacity of
the connected batteries. It can be configured for 0, 25, 50, 75 and 100%. The default setting is 50
%. 100% indicates that charging current is about 15Amps.
c.
Nominal Output Voltage: Configures the correct electricity/voltage supplied in the area/country
where the EPS will be used. 220V, 230V and 240V may be selected. The system default setting is
230V.
Function description: AVR Dynamic Voltage Compensation works automatically based on the
system voltage settings.
d.
Static Frequency Tolerance: There are 6 settings (1,2,4,6,8,10%), and the default setting is +/-6
%.
Function description: The settings may be adjusted to the quality of the electricity in use.
e.
Slew Rate: Also called Dynamic Frequency Tolerance. There are 5 different settings
(0.25,0.5,1,2,4 Hz/Sec). The default value is 4Hz/sec.
Function description: "Slew Rate" indicates the tolerance of a device in accepting frequency
variances. The lower "Slew Rate" results in less tolerance but better protection for the connected
loads.
f.
Low Battery Shutdown Voltage: This function adjusts the EPS shutdown point according to the
battery voltage. The default setting is 10.8V (with load).
g.
Mode Select: The standard mode (setting: 2) and the robust mode (setting: 1) are provided to
select. Using the generators is suggested to select the robust mode (setting: 1), and using the
computers is suggested to select the standard mode (setting: 2). The system default setting is
standard mode (setting: 2).
The settable items are sorted by unit as in the following table:
Delay Time
Charging Current
Nominal Output Voltage
Static Frequency Tolerance
All manuals and user guides at all-guides.com
Items
Unit
Icon Lit
Min
ON BAT
%
ON BAT
V
NORMAL MODE
%
NORMAL MODE
9