All manuals and user guides at all-guides.com
Model
Capacity (VA)
Capacity (Watts)
Operation Technology
AC Input
Input Voltage Range
Input Frequency Range
AC Output
Number of Phase
On Battery Typical
Output Voltage
Nominal Output
Voltage Configuration
Note
On Battery Output
Frequency
Overload Protection
Transfer Time
Output Receptacles
External Battery
Voltage x
Recommended Rating
x Quantity
External Battery Rating
External Battery Type
External Battery
Protection
Hot Swappable
External Battery
Status Indication
Indicators
Audible Alarms
Environment
The unit is not
connected to an AC
outlet.
The battery is worn
out.
Mechanical problem.
TECHNICAL SPECIFICATIONS
AVR ( Double Boost & Single Buck )
0 ~40% LOAD Pure Sine Wave at 230Vac +/- 5%
40~100% LOAD Trapezoidal Wave at 230Vac+/- 5%
Configurable for 220 / 230 / 240Vac
On Utility: Circuit Breaker
On Battery: Internal Current Limiting
Sealed Maintenance Free Lead Acid Battery
On Battery, Low Battery, Overload
12
The unit must be connected to a
220/230/240V outlet.
Contact CyberPower Systems about
replacement batteries.
Contact CyberPower Systems via phone or
visit our website at
CPS1000E-FR
1000VA
700W
140Vac – 300Vac
45~65Hz (auto sensing)
Single Phase
50 / 60 Hz +/- 1%
< 10 ms ( Typical )
FR Type * 2
12V x 100Ah x 1
12V
Fuse & Relay
Yes
Power On, LCD Display
www.cpsww.eu