NVENT RAYCHEM CS-150-UNI-PI
(CW-C/S-150)
ENGLISH
PTB 09 ATEX 1067 U
CS-150-UNI-PI:
II 2 G Ex eb IIC Gb
II 2 D Ex tb IIIC Db IP66
IECEx PTB 09.0042U
Ex eb IIC Gb
Ex tb IIIC Db IP66
PTB 08 ATEX 1102X
XPF, XPI & XPl-S
II 2 G Ex eb 60079-30-1 IIC T2 ... T6 Gb
System Approval:
II 2 D Ex tb 60079-30-1 IIIC T260 ... T90°C Db
IECEx PTB 08.0051X
Ex eb 60079-30-1 IIC T2 ... T6 Gb
Ex tb 60079-30-1 IIIC T260 ... T90°C Db
Baseefa15ATEX0158U
XPF, XPI & XPl-S
II 2 G Ex 60079-30-1 IIC Gb
Bulk:
II 2 D Ex 60079-30-1 IIIC Db
IECEx BAS 15.0105U
Ex 60079-30-1 IIC Gb
Ex 60079-30-1 IIIC Db
TC RU C-BE.ИМ43.В.01854
Ex e II Gb U
Ex tb IIIC Db U
Ta –55°C...+180°C
ООО "ТехИмпорт"
Special conditions for safe use:
1 The components of the connection system, nVent
RAYCHEM type CS-150-UNI-PI (CW-C/S-150), are
used for installation with single core plastic-insulated
heating conductors.
2 Only heating conductors should be used that are
provided with a separate EC type examination
certificate ("ATEX generation"). The installation
instructions and technical data provided have to be
considered.
3 The manufacturer shall prove that suitable measures
have to be taken to safeguard safe and permanent
clamping of heating conductors of a small cross
section.
4 The temperature class of each heat-tracing system
shall be established separately.
5 The specific heating rate of the heating system shall
be established with due regard to the voltage and
spec. conductor resistance variations. Due regard
shall also be given to the permissible current ratings.
6 The connecting cable(s) shall be selected with due
regard, above all, to the max. current rating, the
permissible diameter of the rubber gaskets and the
temperature conditions.
7 The required rubber gaskets shall be selected on
the basis of the specifications in these installation
instructions.
8 The cables connected to the kit shall be secured on
both sides of the kit to permanently provide pull out
protection.
2 | nVent.com/RAYCHEM
Rated insulation voltage
(between L and PE, and L and N)
Variants S and C: 750 V
Variant L: 420 V
Max allowed current: (continuous)
Variant S: 32 A
Variant C with 1 x 2.5 mm
cold lead 25 A
2
Variant C with 1 x 4 mm
cold lead 32 A
2
Variant L with 3 x 2.5 mm
cold lead 25 A
2
Maximum operating temperature:
180°C power on
200°C power off
(Variant L is dependant on the type of cold lead used:
e.g. 200°C for Silicon cold lead, unless the 3 core cold
lead is installed away from the surface to be heated,
such that the limiting temperature of the cold lead is not
exceeded)
Ambient Temperature:
–50°C to +40°C (–58°F to +104°F)
Storage and transportation
Store and transport product in a clean, dry place
Store and transport at temperatures between –55°C
and +40°C
Protect product from moisture, direct sunlight and
mechanical damage
ATTENTION: to avoid danger of electrical shock or
fire, the product must be installed in accordance with
these instructions.
Ingress of moisture has to be avoided before and
during installation.
RCD's are required for all heating circuits. Read
instructions completely before starting installation.
This product does not require maintenance. Damaged
units shall be replaced. Do not use other parts or
duct tape.
Avoid eye contact with lubricant.
Respect the safety data sheet.