1. Data given by manufacturer of cold lead concerning the
minimum and maximum temperatures of use, including
reduction factors (if given) must be considered during design
and installation.
2. When selecting cross section, maximum voltage drop has to
be considered.
3. It is possible that the maximum usage temperature of the
CS-150-UNI-PI will be reduced due to the maximum allowed
usage temperature of the cold lead, unless the cold lead is
installed in sufficient distance away from the surface to be
heated, so that this maximum allowed usage temperature of
the cold lead will not be exceeded.
The connected cables must be secured on both sides of the kit.
The connected cables must be secured on both sides of the kit.
DEUTSCH
1. Angaben des Herstellers der An schluß lei tung zur minimalen
und maximalen Montage- bzw. Betriebstemperatur inklusive
eventueller Reduktionsfaktoren müssen bei der Planung und
bei der Montage beachtet werden.
2. Bei der Auswahl des Querschnitts ist der max. zulässige
Spannungsfall zu beachten.
3. Die max. Einsatztemperatur von CS-150-UNI-PI kann sich
durch die max. zulässige Dauergebrauchstemperatur
der Zuleitung reduzieren, es sei denn die Zuleitung
wird so verlegt (in ausreichendem Abstand von der zu
beheizenden Oberfläche), dass diese max. zulässige
Dauergebrauchstemperatur nicht überschritten wird.
Die angeschlossenen Kabel müssen auf beiden Seiten des
Bausatzes befestigt werden.
Configuration C
Configuration L
Die angeschlossenen Kabel müssen auf beiden Seiten des
Bausatzes befestigt werden.
nVent.com/RAYCHEM | 17