4.3.1
Versatronic Standard
For the tables for the EC or ES version, see
on page 17
Measuring
Inputs and
channel
outputs
Channel 1
IN 7 *
or alternatively
IN 6
PWR 24 V
IN 1
IN 4
OUT 3
OUT 14 ****
or alternatively
channel 2 OUT 14/15
OUT 4
Channel 2
IN 8 **
or alternatively
IN 12
IN 2
IN 5
OUT 2
OUT 15 ****
or alternatively
OUT 14/15
OUT 5
Channel 3
IN 9
IN 3
IN 11
OUT 12
OUT 16/17
Channel 4
IN 10
IN 13
IN 12 ***
or alternatively
channel 2 IN 12
OUT 13 *
OUT 18/19
All channels OUT 1
* If no measuring module is inserted in plug-in connection IN7, the assignment of the measurement signal source from channel 1 is
automatically switched to IN 6.
If no measuring module is inserted in plug-in connection IN8 and an input board is present in plug-in connection IN12, the assignment
of the measurement signal source for channel 2 changes from IN8 to IN12.
Universal input IN12 can be used as temperature input for channel 4 only if the input is not already used as standard signal input 2 for
measuring channel 2.
Ä Chapter 5.2 'Material code'
Explanation
Channel 1 input measurement signal (analogue
input)
Channel 1 input measurement signal, standard
signal input 1
Channel 1 power supply, standard signal input 1
Channel 1 input enable signal
Channel 1 input temperature
Channel 1 controller output 1 (change-over contact)
Channel 1 controller output 2 (normally open
contact)
Channel 1 standard signal output
Channel 2 input measurement signal (analogue
input)
Channel 2 input measurement signal, standard
signal input 2
Channel 2 input enable signal
Channel 2 input temperature
Channel 2 controller output 1 (normally open
contact)
Channel 2 controller output 2 (normally open
contact)
Channel 2 power supply, standard signal input 2
Channel 2 standard signal output
Channel 3 input measurement signal (analogue
input)
Channel 3 input enable signal
Channel 3 input temperature
Channel 3 controller output 1 (normally open
contact)
Channel 3 standard signal output
Channel 4 input measurement signal (analogue
input)
Channel 4 input enable signal
Channel 4 input temperature
Channel 4 controller output 1 (normally open
contact)
Channel 4 standard signal output
Common alarm output for all channels
11
Unit description
Option board
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
417102279 Rev. 4-07.2023