rough framing - before appliance installation
EN
see-thru
1" [25mm] minimum
all sides for sections
of vertical venting.
When passing
through a
ceiling, use
firestop spacer
W500-0028 (not
supplied)
73"
minimum
Horizontal vent sections: A minimum clearance of 3" (76mm) on the top outside of the enclosure and 2" (51mm)
on the sides and bottom outside of the enclosure all around the vent pipe on all horizontal runs to combustibles is
required. Horizontal vent sections within enclosures require a minimum clearance of 6"(152mm) at the top of the
vent pipe.
Vertical vent sections: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to combustibles is
required except for clearances in appliances enclosures. Vertical vent sections within enclosures require a minimum
clearance of 1" (25mm) around the vent pipe.
note:
The L series requires a minimum enclosure height of 73" (185.4cm) measured from the bottom of the appliance.
For temperature requirements, this area must be left unobstructed. Some venting configurations that require
more vertical rise will require a larger enclosure to provide minimum vertical clearance between vent pipes and
combustibles. It is also recommended that the enclosure be ventilated at the top and bottom to circulate the
hot air.
26
W415-1707 / B / 06.04.18
All manuals and user guides at all-guides.com
14"
(35.6cm)
min.
SAFETY BARRIER
note:
Shaded components (finish framing) must be
non-combustible materials.
3" [76mm] top (outside of enclosure)
2" [51mm] sides / bottom (outside of enclosure)
6" [152mm]
minimum
(inside enclosure)
3" [76mm] top (out-
side of enclosure)
2" [51mm] sides /
bottom (outside of
enclosure)
0" to non-
combustible finishing
such as brick and
stone
When passing
through a wall, use
firestop spacer
W615-0162 (sup-
plied with W010-
4178 firestop spacer
assembly)
0" to side standoffs
1/2" finishing flange
(4 sides)
0" to base of the
appliance