4.1.1 minimum clearance to combustible enclosures
single-sided
1" [25mm] minimum
all sides for sections
of vertical venting.
When passing through
a ceiling, use firestop
spacer W500-0028
(not supplied)
minimum
0" to side standoffs
1/2" finishing flange
0" to bottom of the
appliance
Horizontal vent sections: A minimum clearance of 3" (76mm) on the top outside of the enclosure and 2" (51mm) on
the sides and bottom outside of the enclosure all around the vent pipe on all horizontal runs to combustibles is required.
Horizontal vent sections within enclosures require a minimum clearance of 6"(152mm) at the top of the vent pipe.
Vertical vent sections: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to combustibles is required
except for clearances in appliances enclosures. Vertical vent sections within enclosures require a minimum clearance of
1" (25mm) around the vent pipe.
note:
The L series requires a minimum enclosure height of 73" (185.4cm) measured from the bottom of the appliance.
For temperature requirements, this area must be left unobstructed. Some venting configurations that require
more vertical rise will require a larger enclosure to provide minimum vertical clearance between vent pipes and
combustibles. It is also recommended that the enclosure be ventilated at the top and bottom to circulate the
hot air.
All manuals and user guides at all-guides.com
rough framing - before appliance installation
73"
note:
Shaded components (finish framing) must
be non-combustible materials.
3" [76mm] top (outside of enclosure)
2" [51mm] sides / bottom (outside of enclosure)
6" [152mm] minimum
(inside enclosure)
3" [76mm] top (outside
of enclosure)
2" [51mm] sides /
bottom (outside of en-
closure)
0" to non-combustible
finishing such as brick
and stone
When passing through
a wall, use firestop
spacer W615-0162
(supplied with W010-
4178 firestop spacer
assembly)