5.5
Connecting the hoses
See chapter "Application example(s)" for an example of how to route the
hoses from the product to the tank to be monitored.
Verify that the hoses are not subjected to tensile strain or to other types
of mechanical loads.
1. Use oil- and water-resistant plastic hoses 6 x 2 mm for the measuring line
(red), the suction line (transparent) and the exhaust line (green).
- When the leak detector of existing systems is replaced, you may also
use 4 x 2 mm provided such hoses had been used before the leak
detector is replaced.
- The hose connections of the product are designed for 4 x 2 mm and
6 x 2 mm hoses.
Mounting
2. Plug the EnOcean® wire-
less module into the slot.
When plugging in the
wireless module, ensure
the following:
- The position of the
antenna must be at the
right side (close to the
housing wall).
- All pins must be inserted
into the female connec-
tor.
3. Push the antenna of the
EnOcean® wireless mod-
ule into the two housing
openings of the product.
4. Close the cover of the
product.