EN
5
Mounting
5.1
Preparing mounting
5.1.1
Basic vacuum
The vacuum pump of the leak detector must not exceed the pump capac-
ity of 100 l/h.
1. Generate a vacuum of approx. -80 mbar in the interstitial space. Use an
5.1.2
Tightness test
1. Check for leaks in the interstitial space.
- A slight pressure drop in the first hour is unavoidable. After that, the
5.1.3
Adaptation
INCORRECT PRESSURE IN INTERSTITIAL SPACE
If the operating pressure in the interstitial space does not meet the specifica-
tions, the product may be damaged or destroyed.
•
Verify that the operating pressure in the interstitial space of the tank corre-
sponds to the operating pressure specified in the technical specification.
Failure to follow these instructions can result in equipment damage.
1. Reduce the pressure in the interstitial space to -80 mbar.
If the vacuum is greater when the product is connected, the measuring sys-
tem may be damaged or destroyed.
17
installation pump with a greater capacity for this purpose.
pressure must not drop any more.
Eurovac NV
Mounting
NOTICE