afriso Eurovac NV Notice Technique page 83

Publicité

Les langues disponibles
  • FR

Les langues disponibles

EN
2. Install the hose with a steady gradient towards the tank, avoid bends.
- In the case of outdoor tanks, install the hoses with a gradient of 4 %.
If the hose does not have a steady gradient to the tank or if condensate can
collect in the hose, use a condensate trap at all points of the hose where con-
densate can collect.
1. Do not install any shut-off fittings.
2. In outdoor or underground applications, install the hoses in suitable
shock-resistant and weather-resistant protective pipes.
3. Connect the measuring hose to the measuring line connection of the tank.
4. Connect the exhaust line to the tank vent pipe.
- If an AFRISO Euroflex withdrawal system is used, the exhaust line can
be directly connected to the Euroflex return connection in the case of
single-line operation.
5. Connect the suction line to the hose connection of the interstitial space.
Install a liquid barrier in the suction line. Mount the liquid barrier vertically,
for example, at the manhole cover.
29
Eurovac NV
Mounting
6. Push the cover over the
connections to protect
hose connections.