Télécharger Imprimer la page

Cristec OEM 24V / 60A Mode D'emploi page 17

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 3
3.2.3 Settings for each type of battery
Type of battery
SW5
TYPE-1 BAT.
Calcium Lead Tin
OFF
(e.g.: Delphi/Delco
Freedom)
TYPE-2 BAT.
OFF
Lead Sealed
TYPE-3 BAT.
OFF
Gelled Lead or
Calcium Lead
TYPE-4 BAT.
Open Lead with
ON
maintenance (free
electrolyte)
WINTERING
for TYPE-1 BAT.
OFF
TYPE-2 BAT.
TYPE-3 BAT.
WINTERING
ON
For TYPE-4 BAT.
(*)Voltage on BAT 1/BAT 2 with 10% of rated current and a tolerance of +/- 1%
Voltage on BAT D = BAT 1 or BAT 2 – approx. 0.4V
3.2.4 Settings
The charger's factory settings are:
TYPE-2 BAT. Sealed Lead (see table above)
BOOST in ON position
The installer should set the switches (excluding input and off-load output voltage) and possibly adjust the output voltage using
potentiometer RV1 accessible from outside at the bottom of the charger (use the appropriate tool to turn the screw of the
potentiometer), depending on:
-
the type of battery (contact the battery manufacturer if necessary)
-
intended usage
-
the cross-section and length of the output cables
-
whether or not the boost function is required
For special batteries, call in a professional installer, who will make the specific settings in accordance with the accumulator
manufacturer's specifications and according to the specifics of the installation.
Cristec disclaims any liability in case of damage to batteries or ineffective recharging.
CPS2OEM24V-60ADEA.DOC
Switch position
SW4
SW3
SW2
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
CPS2 OEM 24V/60A
Tension Phase
Boost*
SW1
Boost
30.2V
ON
28.6V
ON
28.1V
ON
ON
27.3V
ON
28.3V
ON
27.3V
Tension Phase
Floating*
28.8V
27.2V
26.8V
26.0V
26.8V
26.0V
17