Maintenance
7
7.3
Opening the burner
Disconnect the electrical supply from the burner.
Remove screw 1) and take out hood 2).
Disengage the articulated coupling 3) from the graduated
sector 4).
Remove screw 5), the split pin 9) and pull the burner back by
about 100 mm on the slide bars 6. Disconnect the probe and
electrode leads and then pull the burner fully back.
Turn it as indicated in the diagram, and insert the split pin 9)
into the hole of one of the two guides so that the burner
remains in that position.
Now extract the gas distributor 7) after having removed the
screw 8).
5
2
1
D8717
6
3
7.4
Closing the burner
Push the burner up to approximately 100 mm from the pipe
coupling.
Remove the split pin 9) and push the burner until it is
approx. 100 mm from the pipe coupling.
Reinsert the cables and slide the burner as far as the stop.
Replace the screws 5) and split pin 9) and carefully pull
the probe and electrode cables outwards until they are
slightly taut.
Re-couple the articulated coupling 3) to the graduated
sector 4).
4
3
9
27
GB
8
7
4
Fig. 38
6463