6 - ACCESSING THE CONTROL UNIT SETTINGS
1. Press and hold the OK key until the display shows the menu
desired
2. Release the OK key: the display will show the first item in the
sub-menu
-PrG
Programming the control unit (chapter 12)
-Cnt
Cycle counter (chapter 11)
-APP
Self-learning of working times (chapter 9)
-dEF
Loading the default parameters (chapter 9)
m
WARNING: in case no operation is carried out for
more than one minute, the control unit exits from the
programming mode without saving any of your setups and
changes, which will get lost.
-PrG
2''
-Cnt
4''
-APP
6''
-dEF
8''
- - - -
10''
7 - QUICK CONFIGURATION
This paragraph concerns a quick procedure to set the control unit
and set it at work immediately.
We recommend following these instructions, in order to
check quickly the correct operation of control unit, motor
and accessories, and then changing the configuration in
case of any non-satisfactory parameter.
1. Call up the default configuration: see chapter 8
2. Set items
dir - StoP - Fot1 - Fot2 - CoS1 - CoS2
according to the safety devices installed on the gate.
For the position of the item menus inside the main menu and
for the options related to each item menu, refer to the
chapter 12.
3. Start the self-learning cycle: see chapter 9-9.1 (AUTOMATIC
LEARNING OF THE RUN LIMITS)
4. Check that the automation work properly and if necessary
modify the configuration of the desired parameters.
All manuals and user guides at all-guidesbox.com
8 - LOADING THE DEFAULT PARAMETERS
If necessary, it is possible to restore all parameters to their
standard or default values (see the final summary table).
m
customised parameters.
1. Press and hold the OK key until the display shows
2. Release the OK key: the display shows
3. Press the
4. Press the OK key: the display shows
5. Press the
6. Press the OK key: all parameters are overwritten with their
d i r
tot
ESC
ESC
- 45 -
PLEASE NOTE: This procedure results in the loss of all
key if it is desired to exit this menu)
i
key: the display shows
i
key: the display shows
default values (see Chapter 12), the control units exits
programming mode and the display shows the control panel.
-dEF
no
Si
-dEF
ESC
(only press the OK
dEF
no
Si
ESC
dEF.