6.9
Operation sequence of the burner
6.9.1
Burner starting
NORMAL FIRING
TL
TR
M V
M P
TA
YP
Y
SM
Key to layout (Fig. 39 and Fig. 40)
MV - Fan motor
MP - Pump motor
SM - Servomotor
TA - Ignition transformer
TL - Limit pressure switch/thermostat
TR - Control pressure switch/thermostat or output regulator
Y
- Light oil/gas valve
YP - Pilot valve
6.10
Final checks (with the burner working)
Open the thermostat/pressure switch TL:
Open the thermostat/pressure switch TS:
the burner must stop.
Rotate the maximum gas pressure switch knob to the mini-
mum end-of-scale position.
Rotate the air pressure switch knob to the maximum end-of-
scale position.
the burner must stop in lockout.
Switch off the burner and disconnect the voltage.
Disconnect the minimum gas pressure switch connector.
the burner must not start
Disconnect the QRI flame sensor wire.
the burner must stop in lockout due to firing failure
Make sure that the mechanical locking systems on the differ-
ent adjustment devices are fully tightened.
All manuals and user guides at all-guides.com
Start-up, calibration and operation of the burner
Fig. 39
6.9.2
Undesired shutdown during operation
If the flame should accidentally go out during operation, the burn-
er will lock out within 1s.
To check the full operating programme, refer to the LMV instru-
ment reference handbook, supplied during the technical service
training.
TL
TR
M V
M P
TA
YP
Y
SM
D9335
31
GB
NO FIRING