APPLICATION FIELD WIRING
WIRING DIAGRAM SHOWN BELOW FOR STANDARD RIELLO 530 SE/C PRIMARY CONTROL BOX
INSTALLATION NOTE: ELECTRONIC AIR SHUTTER REQUIRES A CONSTANT 120V POWER SUPPLY TO THE
AUX TERMINAL, FAILURE TO PROVIDE THIS WILL RESULT IN NO BURNER OPERATION OR AIR SHUTTER
WILL NOT CLOSE.
PLEASE NOTE:
OPERATING LIMIT AND SAFETY LIMIT ARE TWO SEPARATE LIMITS.
Key to lay-out:
1
- Main disconnect fuse
2
- Manual service switch
3
- Safety limit device
4
- Operating limit device
5
- Earth ground connection burner chassis
6
- Burner control remote lock out alarm device - wired & supplied by others
AUX - Auxiliary bub base add-on connector (air shutter)
T - T - 24V thermostat connections - low voltage operated system
MIN. WIRE SIZE:
INSULATED 18 AWG SOLID OR 16 STRD.
PROPER EARTH GROUNDING MEANS REQUIRED
DO NOT activate burner until proper oil line connections have been made, or failure of the pump
shaft seal may occur.
DO NOT activate burner until all safety and operating controls have been wired in series with the
WARNING
burner, as required by local code authorities and/or as specified by the appliance manufacturer.
All manuals and user guides at all-guides.com
AIR SHUTTER
MOTOR
RATED 105° C
ALL WIRING SHOWN PROVIDED BY OTHER.