Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

Installation, use and maintenance instructions
Instructions pour installation, utilisation et entretien
Single stage operation oil burners
GB
Brûleurs à huile à une allure
F
RETROFIT APPLICATIONS ONLY
If this burner is being installed in a packaged unit (ie. burner comes with a boiler or furnace), follow the in-
stallation and set-up instructions supplied with the heating unit, as settings may differ from those shown in
WARNING
this manual.
- The following pages contain information, descriptions and diagrams for the proper installation and wir-
ing of the burner. Please read carefully before attempting final installation.
- This manual is to remain with the final installation designation. It is the installer's responsibility to ensure
that the burner installation and operation instructions mentioned in this manual are followed and operated
within local code authority limits.
POUR APPLICATIONS DE MISE À NIVEAU UNIQUEMENT
Si ce brûleur doit être installé avec un autre appareil avec lequel il est livré (comme une chaudière ou un
four), il faudra suivre la notice livrée avec l'unité chauffante dans la mesure où les instructions peuvent dif-
ATTENTION
férer de celles reportées dans ce manuel.
- Les pages qui suivent contiennent toutes les informations, descriptions et schémas permettant une ins-
tallation et un branchement approprié du brûleur. Veuillez lire attentivement ce manuel avant de procé-
der à l'installation de l'appareil.
- Ce manuel doit être conservé par l'utilisateur de l'appareil. L'installateur doit veiller à ce que les instructions
pour l'installation et le fonctionnement du brûleur reportées dans ce manuel soient respectées et appliquées
selon la loi du pays d'installation de l'appareil.
CODE
3726313
3726394
MODEL - MODÈLE
F10
WITH MANUAL AIR SHUTTER
F10
AVEC OBTURATEUR D'AIR MANUEL
F10
WITH MANUAL AIR SHUTTER
F10
AVEC OBTURATEUR D'AIR MANUEL
TYPE
263T
263T
2902554 (9) - 06/2018

Publicité

Chapitres

Table des Matières
loading

Sommaire des Matières pour Riello F10

  • Page 1 Installation, use and maintenance instructions Instructions pour installation, utilisation et entretien Single stage operation oil burners Brûleurs à huile à une allure RETROFIT APPLICATIONS ONLY If this burner is being installed in a packaged unit (ie. burner comes with a boiler or furnace), follow the in- stallation and set-up instructions supplied with the heating unit, as settings may differ from those shown in WARNING this manual.
  • Page 3 INSTALLLATION PRECAUTIONS WARNING AIR FOR COMBUSTION Do not install burner in room with insufficient air for combustion. Be sure there is an adequate air supply for combustion if the boiler/furnace room is enclosed. It may be necessary to create a window to permit suffi- cient air to enter the boiler/furnace room.
  • Page 4: Table Des Matières

    TABLE OF CONTENTS PACKAGE CONTENTS LIST ..............1 SERIAL NUMBER IDENTIFICATION .
  • Page 5: Package Contents List

    PACKAGE CONTENTS LIST Your Riello 40 burner should include the following parts. Please check to make sure all parts are present before begin- ning the installation. Quantity Description Code Burner chassis with cover 3726313 - 3726394 Universal mounting flange + mounting gasket...
  • Page 6: Technical Data

    230 Watts Motor (rated) 3250 rpm Run Current 2.2 AMP Capacitor 12.5 Microfarads 260V Pump pressure 100 to 200 psi Primary control RIELLO 530 SE/C Ignition transformer 8kV 16mA BURNER AND MOUNTING FLANGE DIMENSIONS D7428 Model F10 Inches 10 5/16...
  • Page 7: Initial Set-Up

    INITIAL SET-UP A) Remove burner and air tube from cartons. Check parts list (inside cover) to ensure all parts are present. B) Remove burner cover by loosing the three screws securing it. Remove control box and air tube cover. C) Remove drawer assembly from air tube, insert nozzle and set Turbulator adjustment for specific input required, then set aside.
  • Page 8: Method 2-Semi-Flange Collar

    A) Insert the two BOLTS (1) into the UNIVERSAL MOUNTING FLANGE (10) from the flat side, ensuring the bolt heads are flush with the flat surface. Secure in place using two special CHROME NUTS (2) provided. B) Position the MOUNTING GASKET (3) between the flat surface of the UNIVERSAL MOUNTING FLANGE (10) and the appliance.
  • Page 9: Electrical Connections

    ELECTRICAL CONNECTIONS It is advisable to leave the control box off the sub-base while com- pleting the electrical connection to the burner. 1) Wire access hole (Use BX electrical connector) 2) Earth ground conductor terminal (Green wire) 3) Hot conductor terminal (Black wire) 4) Neutral conductor terminal (White wire) 5) Strain relief clamp WARNING:...
  • Page 10: Nozzle Placement

    NOTE: Terminal 4 is to be used to activate a remote safety lockout circuit only. A 120V AC source is supplied to Terminal 4 upon lockout. The maximum allowable current draw for this circuit is 1 AMP. IMPORTANT: If a neutral or ground lead is attached to Terminal 4, the control box will be damaged should lockout occur. NOZZLE PLACEMENT A) Determine the proper firing rate for the boiler or furnace units, considering the specific application, and then use the Burner...
  • Page 11: Electrode Setting

    INSTALLATION/REMOVAL OF DRAWER ASSEMBLY A) To remove drawer assembly, loosen SCREW (3), then unplug CONTROL BOX (1) by carefully pulling it back and then up. B) Remove the AIR TUBE COVER PLATE (5) by loosening the two retaining SCREWS (4). C) Loosen SCREW (2), then slide the complete drawer assembly out of the combustion head as shown.
  • Page 12: Oil Line Connections

    Riello manometers and vacuum gauges do not require any adaptors, and can be safely connected to the pump ports. An NPT (metric) adapter must be used when connecting other gauge models.
  • Page 13: Two Line (Lift System)

    TWO LINE (LIFT SYSTEM) A) If a two line system is required, install the By-pass 2 LINE (LIFT) SYSTEM - PIPE LENGTHS plug (4) provided. The by-pass plug is installed in 3/8” OD 1/2” OD the return port (9) of the pump. Feet Meters Feet...
  • Page 14: Pump Purge

    PUMP PURGE NOTE To protect the pump gears, it is advisable to lubricate the pump prior to purging a lift system. Apply oil through the VACUUM PORT (C). A) SINGLE LINE (GRAVITY FEED SYSTEM) A) Loosen the bleeder valve (A) until oil flows out. Tighten the bleeder valve securely and start burner.
  • Page 15: Setting The Air Adjustment Plate

    SETTING THE AIR ADJUSTMENT PLATE A) Regulation of the combustion air flow is made by adjustment of the manual AIR ADJUSTMENT PLATE (1) after loosening the FIXING SCREWS (2 & 3). The initial setting of the air adjustment plate should be made according to Column 5 in the Burner Set-up Chart.
  • Page 16: Ducted Combustion Air Intake Applications

    Use a 4” to 6” pipe adapter (not supplied in the kit) to use a 6” diameter pipe. The settings of the burner must be according to the BURNER SETUP CHART – AIR INTAKE APPLICATIONS below. MODEL F10 BURNER SETUP CHART with 4" diameter pipe 20 Ft.
  • Page 17: Burner Start-Up Cycle

    COMBUSTION CHAMBER Follow the instructions furnished by the boiler/furnace manufacturer. Size retrofit application according to the appropriate installation codes (eg. CSA B139 or NFPA #31). BURNER START-UP CYCLE Normal Lock-out, due to light-failure Thermostat Motor Ignition transformer Valve Flame Lock-out lamp D5229 ~ 12 s ~ 12 s...
  • Page 18: Exploded Spare Parts List

    EXPLODED SPARE PARTS LIST 2902554...
  • Page 19: Spare Parts List

    SPARE PARTS LIST CODE DESCRIPTION CODE DESCRIPTION • • • 3020509 BURNER BACK COVER 3949071 SHORT COMBUSTION HEAD 5” (273T1) • • • 3007234 BURNER BACK COVER 3006978 TURBULATOR DISC • • • • 3006992 PIPE CONNECTOR - SUPPLY 3006966 ELECTRODE SUPPORT •...
  • Page 20: Burner Start-Up Form

    BURNER START- UP FORM * Burner S/N. or Model: Appliance: Installer name: Company: Installation date: Address: Phone: Fax: Owner Name: Address: Phone: E-mail: Burner Start-up Info (OIL) Nozzle info: Pump pressure: Air setting: Turbolator setting: Draft overfire: Draft breech: Smoke density: (Bacharach) Single line: Two lines:...
  • Page 21 PRÉCAUTIONS POUR L'INSTALLATION ATTENTION AIR POUR COMBUSTION Ne pas installer le brûleur dans une salle n'ayant pas assez d'air pour la combustion. Assurez-vous qu'il y ait une alimentation en air adéquate pour la combustion si la salle de la chaudière/four est encastrée. Il peut être nécessaire de créer une fenêtre pour permettre à...
  • Page 22 INDEX CONTENU DE L'EMBALLAGE ..............1 IDENTIFICATION DU NUMÉRO DE SÉRIE .
  • Page 23: Contenu De L'emballage

    CONTENU DE L'EMBALLAGE Votre brûleur Riello 40 doit être composé des pièces suivantes. Veuillez contrôler la présence de toutes les pièces énu- mérées ci-après avant de procéder à l'installation de l'appareil. Quantité Description Code Châssis brûleur avec capot 3726313 - 3726394...
  • Page 24: Données Techniques

    3250 tours/min. Courant de cycle 2,2 AMP Condensateur 12,5 Microfarads 260V Pression de la pompe 100 à 200 psi Commande primaire RIELLO 530 SE/C Transformateur d'allumage 8kV 16mA DIMENSIONS DU BRÛLEUR ET DE LA BRIDE DE MONTAGE D7428 Modèle F10...
  • Page 25: Préparation

    PRÉPARATION A) Enlever le brûleur et le tube d'air des cartons. Contrôler que toutes les pièces de la liste du contenu de l'emballage (à l'intérieur du capot) sont présentes. B) Enlever le capot du brûleur en desserrant les trois vis de fixation. Enlever la boîte de contrôle et le capot du tube d'air. C) Enlever le tiroir du tube d'air, introduire le gicleur, régler le turbulateur pour l'entrée voulue puis mettre de côté.
  • Page 26: Méthode 2 - Collier Avec Demi-Bride

    A) Introduire les deux BOULONS (1) dans Ia BRIDE DE MONTAGE UNIVERSELLE (10) depuis le côté plat, en veillant à ce que les têtes des boulons soient au même niveau que la surface plane. Les solidariser à l'aide des deux ÉCROUS CHROMÉS (2) spéciaux livrés avec l'appareil.
  • Page 27: Connexions Électriques

    CONNEXIONS ÉLECTRIQUES Il est conseillé d'enlever la boîte de contrôle de la sous-base lors de la réalisation de la connexion électrique au brûleur. 1) Trou d'accès des câbles (Utiliser le connecteur électrique BX) 2) Borne de conducteur de masse à la terre (Câble vert) 3) Borne de conducteur chaud (Câble noir) 4) Borne de conducteur neutre (Câble blanc) 5) Serre câble...
  • Page 28: Installation Du Gicleur

    REMARQUE: La borne 4 doit être utilisée pour activer un circuit de mise en sécurité distant uniquement. Une source AC 120V est four- nie à la borne 4 lors de la mise en sécurité. Le courant maximum autorisé de tirage pour ce circuit est de 1 AMP. IMPORTANT: Si un câble neutre ou de terre est fixé...
  • Page 29: Réglage De L'électrode

    INSTALLATION/DÉMONTAGE DU GROUPE TIROIR A) Pour enlever le groupe tiroir, desserrer la VIS (3), puis débrancher la BOÎTE DE CONTRÔLE (1) en la tirant délicatement vers l'arrière puis vers le haut. B) Enlever la PLAQUE DU CAPOT DE TUBE D'AIR (5) en desserrant les deux VIS de retenue (4). C) Desserrer la VIS (2), puis faire glisser le groupe tiroir complet hors de la tête de combustion comme indiqué.
  • Page 30: Raccordement Des Tuyaux D'huile

    Les manomètres et les vacuomètres Riello n'ont pas besoin d'adaptateurs et peuvent être branchés aux orifices de la pompe en toute sécurité. Les adaptateurs NPT (métriques) doivent être utilisés en cas de branchement d'autres modèles de manomètre.
  • Page 31: Deux Tuyaux (Système De Relevage)

    DEUX TUYAUX (SYSTÈME DE RELEVAGE) A) Si un système à deux tuyaux est requis, installer le LONGUEURS DE TUYAUX DU SYSTÈME À DEUX TUYAUX (RELEVAGE) bouchon de dérivation (4) fourni. Le bouchon de dérivation est installé dans l'orifice de retour (9) de 3/8”...
  • Page 32: Purge De La Pompe

    PURGE DE LA POMPE REMARQUES Afin de protéger les engrenages de la pompe, il est recommandé de lubrifier la pompe avant de purger le système de relevage. Huiler le RACCORD DE VIDE (C). A) UN TUYAU (SYSTÈME D'ALIMENTATION PAR GRAVITÉ) A) Desserrer le purgeur (A) jusqu'à...
  • Page 33: Réglage De La Plaque De Réglage D'air

    RÉGLAGE DE LA PLAQUE DE RÉGLAGE D'AIR A) La régulation du flux d'air de combustion est effectuée par ajustement de la PLAQUE DE RÉGLAGE D'AIR (1) après avoir desserré les VIS DE FIXATION (2 & 3). Le réglage initial de la plaque de réglage d'air doit être effectué...
  • Page 34: Applications De Prise D'air De Combustion Canalisées

    Les réglages du brûleur doivent être effectués conformément aux spécifications figurant dans le TABLEAU DE RÉ- GLAGE DU BRÛLEUR – APPLICATIONS DE PRISE D'AIR ci-dessous. TABLEAU DE RÉGLAGE DU MODÈLE DE BRÛLEUR F10 avec tube d'un diamètre de 4". 20 pieds.
  • Page 35: Cycle De Démarrage Du Brûleur

    CHAMBRE DE COMBUSTION Respecter les instructions fournies par le fabricant de la chaudière/four. Adapter l'application de mise à niveau selon les codes d'installation appropriés (par exemple CSA B139 ou NFPA #31). CYCLE DE DÉMARRAGE DU BRÛLEUR Normal Blocage, dû à une anomalie d'éclairage Thermostat Moteur Transformateur...
  • Page 36: Catalogue Éclaté Des Pièces Détachées

    CATALOGUE ÉCLATÉ DES PIÈCES DÉTACHÉES 2902554...
  • Page 37: Catalogue Des Pièces Détachées

    CATALOGUE DES PIÈCES DÉTACHÉES CODE N°DESCRIPTION CODE DESCRIPTION • 3020509 CAPOT ARRIÈRE BRÛLEUR 3949071 • • TÊTE DE COMBUSTION COURTE 5” (273T1) • • • 3007234 CAPOT ARRIÈRE BRÛLEUR 3006978 DISQUE TURBULATEUR • • • • 3006992 CONNECTEUR DE TUYAU - ALIMENTATION 3006966 SUPPORT D'ÉLECTRODE •...
  • Page 38: Formulaire De Démarrage Du Brûleur

    FORMULAIRE DE DÉMARRAGE DU BRÛLEUR * Référence ou modèle de brûleur: Appareil: Nom de l'installateur: Société: Date d'installation: Adresse: Téléphone: Fax: Nom du propriétaire: Adresse: Téléphone: E-mail: Infos sur le démarrage du brûleur (OIL) Info sur le gicleur: Pression de pompe: Réglage de l'air: Réglage turbulateur: Tirage au dessus du feu:...
  • Page 40 RIELLO S.p.A. I-37045 Legnago (VR) Tel.: +39.0442.630111 http:// www.riello.com RIELLO BURNERS NORTH AMERICA http://www.riello.ca 35 Pond Park Road 2165 Meadowpine Blvd Hingham, Massachusetts, Mississauga, Ontario U.S.A. 02043 1-800-4-RIELLO Canada L5N 6H6 Subject to modifications - Sous réserve de modifications...

Ce manuel est également adapté pour:

263t37263133726394

Table des Matières