BURNER ADJUSTMENT TABLE
NON-RETROFIT APPLICATIONS
If this burner is being installed in a packaged unit (i.e. Burner comes with a boiler or furnace), follow the instal-
lation and set-up instructions supplied with the heating appliance, as settings will differ from those shown in
this manual.
ACTUAL FIRING
RATE ± 5%
GPH
kg/h
1.45
4.7
1.80
5.8
2.10
6.8
2.40
7.8
2.75
8.9
2.95
9.5
2.55
8.2
2.85
9.2
3.00
9.7
3.65
11.8
4.25
13.7
4.85
15.7
5.45
17.6
5.75
18.6
NOZZLE: Monarch R-PLP, Delavan W-B, Danfoss S-B, Steinen SS-S, Hago P.
NOTE
- F10 Burners: a 60° degree nozzle is suggested, however, a 80° degree nozzle may be used in cases
where the flame is unstable at light-off when operated at low ambient temperatures.
- F15 Burners: a 45° degree nozzle is suggested, however, a 60° degree nozzle may be used in cases
where the flame is unstable at light-off when operated at low ambient temperatures.
ATTENTION:
The above set up charts are a starting point only.
The burner and appliance must be properly set up using proper combustion testing equipment.
COMBUSTION CHAMBER
Follow the instructions furnished by the boiler/furnace manufacturer. Size retrofit application according to the appropri-
ate installation codes (e.g. CSA B139 or NFPA #31).
BURNER START-UP CYCLE
Normal
Thermostat
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
2903377
All manuals and user guides at all-guides.com
NOZZLE
SIZE
GPH
1.25 x 60°
1.50 x 60°
1.75 x 60°
2.00 x 60°
2.25 x 60°
2.50 x 60°
2.00 x 45°/60°
2.25 x 45°/60°
2.50 x 45°/60°
3.00 x 45°/60°
3.50 x 45°/60°
4.00 x 45°
4.50 x 45°
5.00 x 45°
~ 12s
PUMP
TURBULATOR
PRESSURE
PSI
Bar
145
10
145
10
145
10
145
10
150
10.4
140
9.8
170
11.6
160
11
150
10
150
10
150
10
150
10
150
10
140
9.6
Lock-out, due to light-failure
~ 12s
11
AIR DAMPER
SETTING
SETTING
1.5
2.7
2.0
2.8
2.5
3.1
3.5
3.4
4.0
4.2
4.5
4.2
0.0
1.8
0.5
2.0
1.0
2.2
1.5
2.6
2.0
3.1
3.0
4.5
4.5
5.2
5.0
5.5
~ 5s
GB
D5229