STEP 5: Select cables and fuses
The voltage rating of fuses must be greater than or equal to the highest supply voltage of the system.
Fuses: The AC supply to the drive must be installed with suitable protection against overload. Failure to
observe this requirement will cause risk of fire.
WARNING
Maximum
continuous
input
Model
current
A
05200250
31
06200330
48.8
06200440
56.6
05400270
29
05400300
29
06400350
36
06400420
46
06400470
60
05500030
4.3
05500040
5.7
05500069
9.3
06500100
13.2
06500150
18.7
06500190
24.3
06500230
29.4
06500290
37.1
06500350
46.9
07200610
67
07200750
84
07200830
105
08201160
137
08201320
166
09201760
205
09202190
260
07400660
74
07400770
88
07401000
105
08401340
155
08401570
177
09402000
232
09402240
267
07500440
45
07500550
62
08500630
83
4
All manuals and user guides at all-guides.com
Fuses
UL
IEC Class
Class CC,
gG or gR
*
J, or T
A
A
40
40
63
60
63
70
40
35
40
35
**
40
63
**
50
63
**
70
63
10
10
10
10
20
20
20
20
32
25
40
30
50
35
50
40
63
50
80
80
100
100
125
125
**
***
200
200
**
***
200
225
**
***
250
250
**
***
315
300
100
80
100
100
125
125
**
***
250
225
**
***
250
225
**
***
315
300
**
***
315
350
50
50
80
80
**
***
125
100
Cables
IEC60364-5-52
2
mm
Input
Output
10
16
25
6
6
10
16
25
0.75
1
1.5
2.5
4
6
10
10
16
35
35
70
95
2 x 70
2 x 70 (B1)
2 x 95 (B2)
2 x 95 (B1)
2 x 120 (B2)
35
50
70
2 x 50
2 x 70
2 x 70 (B1)
2 x 95 (B2)
2 x 95 (B1)
2 x 120 (B2)
16
25
35
Unidrive M200/M201/M300 Step By Step Guide
UL 508C
AWG
Input
Output
8
4
3
8
8
6
4
3
16
14
14
14
10
10
8
6
6
2
1
1/0
3/0
2 x 1
2 x 2/0
2 x 4/0
1
2
1/0
2 x 1
2 x 1/0
2 x 3/0
2 x 2/0
2 x 4/0
4
3
1
Issue Number: 1