Technical specifications
Type
Protection class (as per DIN 40050)
Temperature
• during operation
• during storage/transport
Electromagnetic compatibility
• Interference radiated
• Resistance to interference
AS-i bus connection
• Voltage range (protected against
incorrect polarity)
• Residual ripple
• Max. current consumption
(all valves on)
a) Type CPA..-ASI
- after current reduction
b) Type CPA..-ASI-Z
Load voltage connection
only with type CPA..-ASI-Z
• Rated value
(protected against incorrect polarity)
• Residual ripple
• maximum starting current (at 24 V)
• Starting current for 4 valves after
current reduction
AS-i data (parameter outputs have
no use)
• ID CODE
• IO CODE
• Profile
9804NH
CPA...-ASI-...
IP65 (compl. fitted)
o
o
- 5
... + 50
C
o
o
- 20
... + 70
C
• tested as per EN 55011,
limit class B
• tested as per EN 50082-2
only AS-i power unit with
protection class 3 (PELV)
permitted
DC 26.5 V...31.6 V
≤ 20 mVpp
CPA10
CPA14
135 mA
205 mA
120 mA
165 mA
25 mA
25 mA
DC 24 V + 10% / - 15%
(DC 20.4 V...26.4 V)
≤ 4 Vpp
CPA10
CPA14
110 mA
180 mA
95 mA
140 mA
FH
8H
S-8.F
17