Installation

Unpacking

Delivery Inspection
After removing the carton, carefully inspect the transfer
switch components for any damage that may have occurred
during shipment.
IMPORTANT: If loss or damage is noted at time of delivery,
have the person(s) making delivery note all damage on the
freight bill and affix his signature under the consignor's
memo of loss or damage. If loss or damage is noted after
delivery, contact the carrier for claim procedures. Missing or
damaged parts are not warranted.
Shipment Contents
• Automatic Power Transfer Switch
• Two Current Transformers
• Installation and Operator's Manual

Mounting Guidelines

The Automatic Transfer Switch is enclosed in NEMA Type 3R
enclosures suitable for indoor or indoor/outdoor use.
— — — — — — Control Wiring
Hot Water
Heater
Figure 1 - Typical Transfer Switch Mounting for Models 071018 and 071019
4
Contactor
Main
Circuit
Breaker
Panel
Branch Circuits
www.mymowerparts.com
Guidelines for mounting the Automatic Transfer Switch
include:
• Install the switch on a firm, sturdy supporting
structure.
• The switch must be installed with minimum NEMA 3R
hardware for conduit connections.
• To prevent switch contact distortion, level and plumb
the enclosure. This can be done by placing washers
between the switch enclosure and the mounting
surface.
• Never install the switch where any corrosive substance
might drip onto the enclosure.
• Protect the switch at all times against excessive
moisture, dust, dirt, lint, construction grit and corrosive
vapors.
A typical installation of the Automatic Power Transfer Switch
for Models 071018 and 071019 is depicted in Figure 1. An
alternative installation of the Automatic Power Transfer
Switch is depicted in Figure 2.
It is best if the transfer switch is mounted near the utility
watt-hour meter, either inside or outside. Discuss layout
suggestions/changes with the owner before beginning the
system installation process.