Télécharger Imprimer la page

Ecoflam Multiflam 1500.1 Mode D'emploi page 32

Bruleurs mixte gaz + fuel lourd
Masquer les pouces Voir aussi pour Multiflam 1500.1:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 46
420010310000 Multiflam 1500.1 - 1800.1 PR/PR
EN
General
Mounting
Connection threads
Inlet end return
To nozzle
Pressure gauge port
Vacuum gauge port
Shaft
Weight
Hydraulic data
Nozzle pressure range
Operating viscosity
Oil temperature
Inlet pressure
Rated speed
Starting torque
Choice of heater
Cartridge
Fitting
Rating
The pressure of the nozzle line is adjusted with the adjusting screw of the TV valve. The oil in excess to nozzle require-
ment is dumped to the return. Two pipe system : oil in excess is returned to tank. One pipe system : oil in excess is
returned to pump suction.
VALVE
IDENTIFICATION
(Not all model combinations are available
Consult your Suntec representative)
TV :
Pressure regulating valve
TV
40
Regulation type :
01 : by screw
02 : by piston,
for modulating purpose
Revision number
Flange mounting
Cylindrical according to ISO 228/1
G 1/2"
G 1/2"
G 1/4"
G 1/4"
Ø 20 mm
7,8 kg (T2)
-
8,1 kg (T3)
8,7 kg (T4)
-
9,4 kg (T5)
40 bars max. (T2, T3, T4)
30 bars max. (T5)
4 - 450 cSt
0 - 150°C max. in the pump
light oil :
0,45 bars max. vacuum to prevent
air separation from oil
heavy oil :
5 bars max.
3600 rpm max.
0,4 N.m
Ø 12 mm
according to DIN 40430, NFC 68190 (N°9 elec.)
80-100 W
PUMP SUNTEC TV TECHNICAL DATA
Pressure range :
10 : 2 - 10 bars
40 : 7 - 40 bars
Oil under suction
01
1
Oil under pressure
By-passed oil
returned to tank,
or to suction
To nozzle
Capacity (L/h)
4200
T5
4000
3800
3600
3400
3200
3000
T4
2800
2600
2400
T3
2200
2000
1800
T2
1600
1400
1200
1000
0
5
10
15
Viscosity =
Data shown are for new pumps, with no allowance for wear.
Power consumption
Oil under pressure
Intake
Return
By-passed oil
To nozzle
Return
TV
valve
T pump
32
Pump capacity
2850 rpm
20
25
30
35
40
Pressure
(bars)
200 cSt
20 cSt
5 cSt -
Rated speed = 2850 rpm
Pressure
adjustment
R
e
u t
n r
o t
suction
To tank
Intake
from Tank

Publicité

loading

Ce manuel est également adapté pour:

Multiflam 1800.1