4. 4-WAY MOTORIZED VALVE
4.1 Servomotor technical data.
Power supply:
230 V / 50 Hz
Consumption:
4 VA
Degree of protection:
IP 55
Insulation class:
II
Max torque:
14,5 Nm (230 V)
Rotation angle:
90/270°
Manoeuvre time:
60/180 sec
Auxiliary contact:
1 - free 5 A, 230 V (on/off)
Operating temperature:
da 0 °C a 50 °C
Indicator:
open valve - diverted flow
Continuous manoeuvre frequency: 1/10 min.
Note
The servomotor is provided with an auxiliary contact to manage the
enabling of a user (e.g., boiler, meter, circulation pump).
4.2 Valve technical data.
Brass body:
ST UNI EN 12165 CW617N nickel-plated
Brass sphere:
ST UNI EN 12165 CW617N chrome-plated
Operating limits:
da -40 °C a 100 °C (circulating fluid)
Operating pressure:
PN 40
Differential pressure:
max 6 bar
Sphere housing seal:
PTFE
Rod seal:
HNBR
4.3 Installation.
The flow direction indicator installed on the valve must always be orien-
ted in the same direction as the system flow at the time the motor is
installed.
The motor can be installed with the cable outlet either on the right or on
the left of the valve itself without affecting the operation of the micro-
switch.
/ IP 50
Use a fixed wrench to perform one complete turn of the manoeuvre rod
of the valve.
Check and align, if necessary, the metal joint at the outlet of the servo-
motor with the manoeuvre rod of the valve; check that the servomotor is
perpendicular to the valve.
4.4 Wiring diagrams.
Wiring diagram for connection of a user U powered at 230 V (5 A max)
through the valve motor.
GRAY
GRAY
BLACK
BROWN
BLUE
Wiring diagram for connection of a user U with independent power supply
(max 230 V - 5 A).
GRAY
GRAY
BLACK
BROWN
BLUE
Key
a Room thermostat
b User
c Auxiliary contact
d Electrical bridge
GB
GB
230V
F N
TA
230V
F N
TA
21