LERBAKKEN 10, 8410 RØNDE DENMARK
9410
For safe installation of 9410 the following must be observed. The module shall only be
Installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
9410 Power Control Unit
ATEX Certificate
Marking:
Standard:
Non Hazardous Area or Zone 2
T4: -20 ºC <Ta < +60ºC
91 92 93 94 95
Status
24 V
GND
Revision date:
2008-06-10
ATEX Installation drawing
KEMA 07ATEX0152 X
3G Ex nA nC IIC/IIB/IIA T4
EN60079-0:2006, EN60079-15:2005
34
Backup -
33
Backup +
32
Supply +
31
Supply -
14
13
NC
12
COM
11
NO
9410
Version Revision
V2 R1
9410 - Product Version 9410-001
Terminal 34-33
Backup: 21,6 VDC – 26,6VDC / 4ADC
Terminal 31-32
Supply: 21,6 VDC – 26,6VDC / 4ADC
Terminal 11, 12, 13
Power Rail Status Relay
Unclassified installation
250VAC, 2A, 500VA / 30VDC, 2A, 60W
Zone 2 installation:
32VAC, 2A, 64VA / 30VDC, 2A, 60W
Power
Rail
Prepared by:
PB
9410QA01
Page:
1/3