Gas Supply

The range must be connected to a regulated gas supply.
The supply line must be equipped with an approved exter-
nal gas shut-off valve located near the range in an acces-
sible location. Do not block access to the shut-off valve.
Refer to the illustration below.
A compatible ISO 7-1 gas inlet thread is provided on all
units. Contact your local Wolf dealer if an ISO 228-1 or
other gas inlet thread is required. Pipe joint compounds,
suitable for use with LP gas should be used. For LP gas,
piping or tubing size can be 13 mm minimum. LP gas sup-
pliers usually determine the size and materials used on the
system. Gas connection at rear of the appliance is 1/2" BSP.
If local codes permit, a flexible metal appliance connec-
tor is recommended for connecting this range to the gas
supply line. Do not kink or damage the flexible connector
when moving the range.
If rigid pipe is used as a gas supply line, a combination of
pipe fittings must be used to obtain an in-line connection
to the range. All strains must be removed from the supply
and gas lines so the range will be level and in line.
The appliance and its shut-off valve must be disconnected
from the gas supply piping system during any pressure
testing of the system at test pressures in excess of .5 psi
. The appliance must be isolated from the gas
(3.5 kPa)
supply piping system by closing its individual manual shut-
off valve during any pressure testing of the system at test
pressures equal to or less than .5 psi
.
(3.5 kPa)
Wolf natural gas ranges will function up to 3124 m in alti-
tude without adjustment and LP gas ranges will function
up to 2621 m.
SHUT-OFF VALVE
OPEN POSITION
TO APPLIANCE
GAS SUPPLY
Gas shut-off valve
GAS RATING
Note: This appliance is fitted with an internal regulator the operating pressure is
Natural - 0.8 kpa / Propane - 2.5kpa
The regulator is preset at the factory and should not require adjustment. If required refer to Access to TPP
appendix supplied with this manual.
Commissioning Procedure - Set the 4 Left-hand side burners 2 x Semi rapid / 1 x Rapid / 1 x Auxiliary to
high and adjust regulator to 0.8kpa for Natural Gas and 2.5kpa for Propane.
Gas Certification No AGA9025G