O p e r a t i o n
6.1

Control unit

Observe the installation and operating instructions for the control unit used.
6.2

Gravity brake

7
M a l f u n c t i o n s / t r o u b l e s h o o t i n g
If an error message is output, it appears on the control unit display.
Please observe the corresponding instructions for the control unit.
Malfunction
Pump noise
Insufficient tapping quantity
Insufficient tapping
temperature
Drinking water does not heat
up
908.19.08.00
Last updated 2022/03/15
A gravity brake is installed in the heating
return to prevent incorrect circulation.
(see fig.)
The heat exchanger is to be vented
during the commissioning process by
using the manual vent valve.
Possible cause
Air in the system
Insufficient water pressure
Calcification in heat
exchanger
Incorrect adjustment on the
control unit
Excessive pressure loss in
the piping on the heating side
Control unit not in operation.
Air in the system.
HW flow sensor not
connected correctly, or
defective.
Heating flow temperature
sensor not connected
correctly or faulty.
Pump faulty
Flow rate sensor defective
- 13 -
Remedy
Bleed
Check pressure, increase if
necessary
Decalcify/replace
Check settings
Check the piping, change if
necessary
Check control unit
Bleed
Check, replace if applicable
Check, replace if applicable
Check, replace if applicable
Check and replace if
applicable