Operation; Circulation Pump; Function Of The Gravity Brake And Ball Valves - Tuxhorn tubra-PGR-S DN 20 Instructions De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5
O p e r a t i o n
5.1

Circulation pump

Observe the operating manual of the circulation pump.
5.2

Function of the gravity brake and ball valves

The gravity brake is installed in the return ball valve
Operational position
Draining/Filling
„Closed" position
Art.-Nr. 966.20.27
Last updated 2022/02/28
The ball valves are open.
The key areas are vertical.
To open the ball valve, it must be turned in
the "on" position by turning the spindle 90 °
counterclockwise with a 12 mm open-end
wrench.
To prevent gravity circulation, the valve disk
must not be lifted.
The gravity brake is in the operating position
when the wrench flats are vertical.
For filling and complete draining of the sys-
tem, the gravity brake is opened by turning
the valve to the right.
The spindle is at an angle of 45°.
The ball valves are closed.
The key areas are horizontal.
To close the ball valve, it must be set to the
"off" position. To do this, the spindle must be
turned 90 ° clockwise with a 12 mm open-
end wrench.
- 10 -