Technical Data - nVent RAYCHEM TCON-CSD/20 Notice De Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6� TECHNICAL DATA
Meas� input
Designation
Resistance
Pt100 EN 60 751
thermometer
Pt1000 EN 60 751
KTY2X-6 (PTC)
Measuring current with Pt100: 0.2 mA, with Pt1000 and KTY2X-6: 0.02 mA.
Lead compensation is settable via the parameter Lead compensation resistance Of.r.
Total resistance (sensor+lead) must not exceed 320Ω with Pt100.
Current
0 to 20 mA
4 to 20 mA
Input resistance R
≤ 3Ω
IN
Range
Meas� accuracy
ambient
temperature error
–200 to +600°C
0.1%/ ≤100ppm/°C
–200 to +600°C
0.1%/ ≤100ppm/°C
50 to +150 °C
1%/ ≤100ppm/°C
–2 to 22 mA
0.1%/ ≤100ppm/°C
scalable
with S.cLand
S.cH
or customer table
2.4 to 21.6 mA
0.1%/ ≤100ppm/°C
scalable with
S.cL
and
S.cH
/
Recognition of ���
1
Probe
Probe
shortcircuit
break
Yes
Yes
Yes
Yes
Yes
Yes
No
No
3
Yes
Yes
3
nVent.com/RAYCHEM | 20

Publicité

Table des Matières
loading