3

Technical data

3.1
GTF pump
Submersible grey water pump with multi-vane impeller
Information / pump type
Weight
Power P1 / P2
Speed
Operating voltage
Rated current
Max. pumping capacity
Max. pumping height
Max. temperature
Pumping medium
Protection rating
Protection class
Motor protection
Connection type
Connecting cable (10 m)
Type of fuse required (Mono)
Type of fuse required (Duo)
Operating mode
Power and pumping height
(1)
(2)
(3)
(4)
30 / 130
1400
22 kg
1.5 kW / 1.1 kW
1.6 kW / 1.2 kW
230 V; 50 Hz
6.5 A
31 m³/h
49 m³/h
10.5 m
internal
3 x 1.5 mm²
C16 A
C16 A
3 x C16 A
GTF 1600
GTF 2600
GTF 4000
GTF 5200
Pumping station / Installation and operating manual
1600
2600
27 kg
40 kg
2.6 kW / 2.1 kW
2900 rpm
400 V; 50 Hz
2.9 A
4.5 A
46 m³/h
9.3 m
13.6 m
40 °C
IP68 (20 mWs/48 h)
I
external
Direct connection
6 x 1.5 mm²
3 x C16 A
3 x C20 A
S1 / S3
4000
5200
45 kg
56 kg
4.0 kW / 3.4 kW
5.2 kW / 4.4 kW
2835 rpm
6.6 A
8.7 A
52.8 m³/h
52.8 m³/h
18 m
21 m
10 x 1.5 mm²
3 x C20 A
3 x C20 A
3 x C32 A
3 x C32 A
010-992_01