6.4
Installation conforme à UL
REMARQUE
Le chapitre suivant est toujours en anglais, indépendamment de la langue de la pré-
sente documentation et ce en raison des prescriptions UL.
6.4.1
(Field wiring) Power terminals
Use 75 °C copper wire only.
6.4.2
Short circuit current rating
Suitable for use on a circuit capable of delivering not more than 5000 rms symmetrical
amperes when protected by 25 A, 600 V non-semiconductor fuses or 500 V minimum
25 A maximum inverse time circuit breakers.
Max. voltage is limited to 500 V.
6.4.3
Branch circuit protection
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
For maximum branch circuit protection see table below:
Non Semiconductor Fuses (currents are
Model
PHE1.B-A15-...
PHE2.B-A15-...
6.4.4
Motor overload protection
The devices are provided with load and speed-sensitive overload protection and ther-
mal memory retention upon shutdown or power loss.
The trip current is adjusted to 140 % of the rated motor current. For further informa-
tion, refer to chapter "Technical data".
6.4.5
Environmental rating
Type 1
6.4.6
Wiring diagrams
For wiring diagrams, refer to chapter "Electrical installation".
SCCR: 5 kA/500 V
When protected by:
maximum values)
25 A/600 V
Notice d'exploitation – MOVIPRO
Installation électrique
Installation conforme à UL
Inverse-Time Circuit Breaker (currents
are maximum values)
25 A/500 V
®
PHE..B-A15-.1X0..B-00
6
43