Les langues disponibles

15) Profile and Class
Numatics' G2-2 FIPIO node is a Class 0 device and supports 3 different Standard (STD_P) Device Profiles as
defined in the WorldFip FIPIO Standard Profiles:
1.
FIPIO Reduced Device Profile (FRDP)
2.
FIPIO Standard Device Profile (FSDP)
3.
FIPIO Extended Device Profile (FEDP)
The Numatics' G2-2 FIPIO node will automatically select the correct profile for the manifold, based on the
configuration data size resulting from the configuration of the discrete I/O modules. The user must select the
appropriate "Base Module" type in the configuration software.
The table below shows which "Base Module" is required depending on the physical I/O configuration of the
manifold.
Manifold's I/O Size
(1 Word = 2 Bytes)
Up to 2 Input words and 2 Output words
Up to 8 Input words and 8 Output words
Up to 32 Input words and 32 Output words
!
G2-2 Series FIPIO Quick Start Manual
2 Words < Inputs ≤ 8 Words
2 Words <Outputs ≤ 8 Words
If either the Input words or Output words fall into a higher Manifold
I/O size, then the user must choose that higher Manifold I/O Size.
3835058 TDG22FPQS2-0
Subject to change without notice
www.numatics.com/fieldbus
I/O Range
Inputs ≤ 2 Words
and
Outputs ≤ 2 Words
or
Inputs > 8 Words
or
Outputs > 8 Words
1/07
STD_P
Base Module Type
FRD C2
FSD C8
FSD C32